VD120 Series Inverter User Manual Parameter Description
-
123
-
Output
current
Zero current
detection level
Fb-25
Zero current
detection signal
Time
Time
Zero current detection time Fb-26
ON
Fig 6-26 Schematic diagram of zero current detection
Fb-27
Output Current Limit
Exceed
0.0% (no detection)
0.1%~300.0% (rated motor current)
200.0%
○
Fb-28
Output Current Limit
Exceed Detection Delay
Time
0.00s~600.00s
0.00s
○
When the output current of the inverter is greater than or limit exceed detection point, and the
duration is more than the software overcurrent point detection delay time, inverter multi-function DO
output ON signal, the following figure is the output current limit exceed function diagram.
Fb-27
Time(t)
DO
output
Time(t)
Output
current
Fb-28 DO output
Fig 6-27 Schematic diagram of output current limit exceed detection
Fb-29
Any Current Reaching 1
0.0%~300.0% (rated motor current)
100.0%
○
Fb-30
Any Current Reaching 1
Amplitude
0.0%~300.0% (rated motor current)
0.0%
○
Fb-31
Any Current Reaching 2
0.0%~300.0% (rated motor current)
100.0%
○