Parameter Description VD120 Series Inverter User Manual
-
128
-
Count value need to be collect by the multi-function digital input terminals. In the application, need to
set the corresponding input terminals function to "counter input" (function 44), when the pulse
frequency is higher, must use DI5/HDI1 port.
When the count vale reached set count value Fb-59, multi-function digital DO output "set count value
reached" ON signal, then the counter stop counting.
When the count value reached the designated count value Fb-60, multi-function digital DO output
"designated count value reached" ON signal, and the counter continue to count, the counter stop until
the " set count value".
Designated count value Fb-60 shall not be greater than set count value Fb-59. Below is the function
diagram for set count value reached and designated count value reached.
1
2
3
4
5
6
7
8
9
Count pulse
DI5
Set count
DO1
Designated count
relay
Fig 6-31 Schematic diagram of set count valueand designated value
FC Multi-reference and Simple PLC Parameters Group
FC-00
Multi-reference 0
-100.0%~100.0%
0.0%
○
FC-01
Multi-reference 1
-100.0%~100.0%
0.0%
○
FC-02
Multi-reference 2
-100.0%~100.0%
0.0%
○
FC-03
Multi-reference 3
-100.0%~100.0%
0.0%
○
FC-04
Multi-reference 4
-100.0%~100.0%
0.0%
○
FC-05
Multi-reference 5
-100.0%~100.0%
0.0%
○
FC-06
Multi-reference 6
-100.0%~100.0%
0.0%
○
FC-07
Multi-reference 7
-100.0%~100.0%
0.0%
○
FC-08
Multi-reference 8
-100.0%~100.0%
0.0%
○
FC-09
Multi-reference 9
-100.0%~100.0%
0.0%
○
FC-10
Multi-reference 10
-100.0%~100.0%
0.0%
○
FC-11
Multi-reference 11
-100.0%~100.0%
0.0%
○
FC-12
Multi-reference 12
-100.0%~100.0%
0.0%
○
FC-13
Multi-reference 13
-100.0%~100.0%
0.0%
○
FC-14
Multi-reference 14
-100.0%~100.0%
0.0%
○
FC-15
Multi-reference 15
-100.0%~100.0%
0.0%
○