UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
39
Revision 2.05
Of 107
When you press button
and the arrow „
>>
” is visible (
Go to
field is empty) a screen displaying
the parameters of the selected
addressable input appears:
The screen provides the
following information:
−
Number and text of the text
message that will be seen if
the addressable input is
triggered (the message shall
be set in advance);
−
The number of the
addressable outputs that will
be triggered upon activation
of the input;
−
A list of the addressable
outputs or the message No addressable outputs activated by this input.
12.2.10. Menu
Archive
The menu provides information for all events saved in the energy independent memory of the fire
control panel.
The following events are registered in the fire control panel: fire condition, disables, test mode,
fault condition and general conditions. For each event are displayed: number of the event as per the
selected filter (total; fire conditions; fault conditions; period), serial number of the event in the archive,
event code, event time and some specific information depending on the event type.
The code and the specific information for events from the type
Fire condition
are
Event character
Event code
Specific information
Fire alarm zone in Fire
condition stage I upon
activation of a device
Fire1
Fire alarm zone in Fire
condition stage II upon
activation of a device (manual
call point)
Fire2
Response from a device in a
zone already in Fire condition,
without changes in the fire
phase
Fire
Zone number;
Loop where the device is integrated;
Device number in the loop;
Text message of the zone;
Text message of the device
Fire alarm zone in Fire
condition stage II where
Time
Fire Phase 1 – Phase 2
has
expired
Fire 2
Zone number;
Text message of the zone
Fire alarm zone in Pre Fire
Condition
PreFire
Fire alarm zone exited PreFire
PreFire reset
Zone number;
Loop where the device is integrated;
Device number in the loop;
Text message of the zone;
Text message of the device
Fire control panel exited Fire
condition
Fire reset
–
Mode:DAY
17:35:07
Mon 14
Ма
r 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Parameters: Input Lp1
А
ddr9.1
Text message
№
1
Text
Message
List of addressable Outputs
Total: 11
Lp1
А
ddr10.2 Lp1
А
ddr11 Lp1
А
ddr13.3
Lp1
А
ddr10.3 Lp1
А
ddr12 Lp1
А
ddr13.4
Lp1
А
ddr10.4 Lp1
А
ddr13.1 Lp1
А
ddr13.5
Lp1
А
ddr10.5 Lp1
А
ddr13.2