Depending on the result of the verification, the fire control panel would execute the following
operations:
a) if the fire control panel is able to synonymously detect the location of a device in a loop and to
verify its parameters against these saved in the energy independent memory:
♦
the device is placed in service with its previous address in the loop;
♦
the fault
Removed device
is cleared;
b) if the fire control panel is able to synonymously detect the location of a device in a loop, but
the device’s parameters do not conform with these saved in the energy independent memory:
♦
the device is placed in service with an address, corresponding to device’s location in
the loop;
♦
a fault condition due to incompliance with identification number, type or class is
added;
♦
the device is included in the Service zone;
c) if the fire control panel is not able to synonymously detect the location of a device in a loop
(two or more serial devices forming an area are removed, but only some replaced):
♦
the device is placed in service with the first available address from the corresponding
area in the loop;
♦
a fault is added,
Device not initialized
;
♦
the device is included in the Service zone.
When the last device for
Removed devices
area is placed, the fire control panel will
synonymously detect their location. For the last placed device the fire control panel will run operations
a) or b). For previously placed devices the fire control panel will run the following operations:
d) if the fire control panel detects compliance of parameters with these saved in the energy
independent memory:
♦
the device is placed in service with its previous address in the loop;
♦
the faults
Removed device
and
Device not initialized
are cleared;
♦
the device is excluded from the Service zone;
e) if the fire control panel detects incompliance of parameters with these saved in the energy
independent memory:
♦
the device is placed in service with an address, corresponding to device’s location in
the loop;
♦
a fault condition due to incompliance with identification number, type or class is
added;
♦
the device remains in the Service zone.
In cases b), c) and e) the following actions can be taken:
−
if any devices seemed to be involuntarily exchanged, they shall be placed on the proper
locations;
−
the device can be excluded from the Service zone by using the Menu
section 13.7.3) and setting the proper address;
−
to save the new loop configuration by using the Function
When a new addressable device (exceeding the number of addressable devices in the loop), the
fire control panel sets a temporary address for this device (the text message
Reinitialization
appears
on the lower end of the display) but ignores the device during further operation. To include the device
in the loop configuration you need to start the Function
7. Duty Mode
7.1. Description
The fire control panel is in Duty Mode, when it is not in any other of the rest 7 possible conditions.
7.2. Indication
7.2.1. LED and sound indication
In Duty Mode the green LED indicator is activated
(Power supply). The local sounder is off.