UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
7
Revision 2.05
Of 107
DISABLED DEVICE – the addressable device (a fire detector) is switched off and is not
monitored for a fault condition. This feature is user defined. The indication for a disabled device is
common light indication and text messages on the LCD display
DISABLED ZONE – a
zone
that is
not controlled for activated fire detectors and fault condition.
This condition is user defined. The indication for a disabled zone is common light indication and text
messages on the LCD display.
FATAL FAULT CONDITION – fault condition that prevents the fire control panel from continuing
its operation. The indication is common light indication, local sound indication and text messages on
the LCD display.
FIRE ALARM LOOP (further on it will be referred as LOOP) – automatic fire detectors and
addressable manual call points and addressable executive devices, physically connected by the
means of two-wire connection. The basic configuration of IFS 7002 includes two fire alarm loops; a
maximum of 125 devices (addressable fire detectors and/or addressable executive devices) can be
integrated into each loop.
FIRE ALARM ZONE (further on it will be referred as ZONE) – logical unification of automatic fire
detectors and addressable manual call points, physically allocated in fire alarm loops on random
principle. Interactive Fire Control Panel IFS7002 allows for formation of a maximum of 250 zones. Up
to 60 fire detectors can be integrated in each zone.
FIRE CONDITION STAGE I – phase 1 of Fire condition; upon activation of automatic fire detector
the fire control panel enters Fire condition until the specified time expires. The common and local light
indicators, local sound signaling and a text message displayed on the LCD display indicate the phase.
FIRE CONDITION STAGE II – phase 2 of Fire condition; the fire control panel enters Fire
condition stage II when: a) the time for
Fire condition stage I
has expired or b) upon activation of a
manual call point. The common light indicators, local sound signaling and a text message displayed
on the LCD display indicate the phase.
GROUNDS –
non-fatal fault condition
, due to leakage to a grounded wire.
INSPECTION TIME – period of time added to the remaining time, before the system proceeds
from
Fire condition stage I
to
Fire condition stage II
, when button
is pressed. Usually, this
period of time is long enough for the authorized personnel to check up the indicated premises. The
inspection time is user defined and is specified for each
zone
.
INTERRUPTED LOOP OR MONITORED OUTPUT –
non-fatal fault condition
due to current
value in a
loop
or in
monitored output
lower than the threshold value. The user shall define the
threshold value separately for each loop.
LOCAL SOUNDER – a sounder built-in the fire control panel.
LOW BATTERY –
fatal fault condition
due to full discharge of the backup batteries upon
interrupted power supply.
MONITORED OUTPUT – a potential output that monitors the serviceability of the connection
wires between the fire control panel and the executive device. Follow the special diagram for
connection.
NON-FATAL FAULT CONDITION – fault condition that allows the fire control panel to continue
operation. The indication is common light indication, local sound indication and text messages on the
LCD display.