4.5. Monitored outputs
−
Type
- potential
−
Е
lectrical characteristics
- (24±5)V/100mA
4.6. Relay outputs for fire conditions
−
Type
- potential free, switching,
−
Electrical characteristics
- 3A/125VAC; 3A/30VDC
4.7. Relay output for fault conditions
−
Type
- potential free, switching
−
Electrical characteristics
- 3A/125VAC; 3A/30VDC
4.8. Performance
−
Control over fire alarm loops and monitored outputs for fault conditions (short circuit
and interruption) and automatic reset
−
Detection of removed devices in the loops and automatic reset
−
Ability to set the zones in Coincidence Mode
−
Two phases of Fire condition, programmable time for Fire condition stage I,
separately for each zone
−
Option to prolong the time period for Fire condition stage I with programmable
inspection period, specified for each zone
−
Built-in sounder for fire condition – one tonal, discontinuous, can be switched off
−
Built-in sounder for fault condition – one tonal, discontinuous, can be switched off
−
Built-in real time clock
−
Set of test modes and options for adjustment:
♦
Setting the clock;
♦
Check ups on light and sound indications;
♦
Test of fire alarm zones;
♦
Adjustment of outputs and integrated external devices;
♦
Programming of parameters and modes of operation;
♦
Remote programming of the parameters from distant operator control point;
−
Energy independent archive of registered events with the events type, date and hour
– up to 1023 events;
−
Interfaces for communication with external devices - CAN 2.0B and RS-232
(directly or via modem).
4.9. Indications of registered events
−
Light indication
- LED
−
Text messages
- LCD display,
320
х
240 points, backlit
−
Sound signaling
- built-in sounder
4.10. Power supply
4.10.1. Mains
−
voltage
- 220/230V
−
frequency
- 50Hz
4.10.2. Back up batteries
−
battery type
- lead, gel electrolyte
−
number of batteries
- 2 pcs
−
connection
- serial connection
−
nominal voltage of the back up battery
- 24V
−
nominal capacity C
20
-
18Ah
−
extreme discharge voltage
- 21V
−
charge voltage
- 28,2V
4.10.3. Consumption on back up batteries supply
−
at 24V
- < 250mA
−
at 26V
- < 240mA