UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
80
Revision 2.05
Of 107
If the new address is out of the
specified range, button
is
ignored. Otherwise a command
screen appears where you shall
confirm the readdressing:
The following information is
displayed on the screen:
−
The new address that will be
assigned to the device;
−
The text message specified
for this address;
−
Message
Different device ID
– only when the ID number of
the device is different than
the number for this address
saved in the control panel;
−
Message
Different device type
– only when the device type is different than the type saved for
this addres in the control panel;
−
Message
Different device class
– only when the temperature class of the device is different
than the class saved in the control panel.
When you press button
the readdressing is cancelled and the screen for selection of new
address is reverted.
When you press button
the readdressing is completed and the screen for selection of
devices that shall be excluded from the service zone is reverted (or the screen with the message
The
s
ervice zone is empty
).
13.7.4. Menu
Exclude devices
The menu allows the user to
exclude or include separate
addressable devices:
All 250 (125 in each loop)
addressable devices are accessible
whether included physically to the
fire alarm loops or not. In the middle
of the heading is displayed the total
number of devices included in both
loops.
For each device is displayed:
−
Its consecutive number, the
loop it is included in and its
address in the loop – in the
top line;
−
The text message – in the
line beneath.
The devices obtain numbers according to the sequence:
−
Devices in Loop 1 – numbers from 1 t
о
125;
−
Devices in Loop 2 – numbers from 126 t
о
250.
The selected device is pointed by arrow – „
>>
”.
Mode:DAY
9:49:43
Mon 28 Mar 2005
Exclude Devices Devices total: 63
Go to:
>>
1 Lp1
А
ddr1
Point 1.001
2 Lp1
А
ddr2
Point 1.002
3 Lp1
А
ddr3
Point 1.003
4 Lp1
А
ddr4
Point 1.004
5 Lp1
А
ddr5
Point 1.005
6 Lp1
А
ddr6
Point 1.006
0
1
2
3
4
5
6
7
8
9
С
Mode:DAY
18:13:51
Fri 25 Mar 2005
Readdressing
Lp1
А
ddr2
New address:3
Point 1.003
Different Device ID
Different Device Type
Differenet Device Class
Save new Data?
–
confirm
–
cancel