Upon unsuccessful operation
appears the following screen:
Upon successful operation the menu will be exited automatically.
14. Remote Control Mode
14.1. Description
The control panel enters Remote Control Mode when an external control device of higher level
(computer from a centralized Dispatcher Control Point or similar) performs set up of the control panel
configuration parameters via serial interface. All other modes and condition are exited. When in
Remote Control Mode the panel does not provide service to fire alarm zones, addressable devices,
monitored outputs and other periphery devices (all outputs are off); it is under the control of the
external device. Upon exit of Remote Mode reset of the control panel is performed.
14.2. Indication
14.2.1. LED and sound indication
In Remote Mode only the green LED indicator
is illuminated (
Power supply
). The local
sounder is off.
14.2.2.
Т
ext messages
The following screen appears on
the LCD display:
14.3. Keypad
In Remote Mode none of the buttons are active.
Remote control
Mode:DAY
10:38:08
Tue 29 Mar 2005
Clear Archive
Operation unsuccessful!
Would You like to run the Operation again?
–
confirm
–
cancel