UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
26
Revision 2.05
Of 107
12.2.2. Menu
Disables
The menu displays detailed information for disabled zones, disabled addressable devices and
monitored outputs of the fire control panel.
Menu
Disables
contains the following subordinate menus and screens:
−
Screen
Total
– displays information for all disables;
−
Menu
Zones
– displays information only for disabled zones;
−
Menu
Devices
– displays information only for disabled addressable fire detectors;
−
Menu
Outputs
– display information only for disabled outputs (monitored outputs and
addressable output devices).
12.2.2.1. Screen
Total
If no disables are set, the
following screen appears:
Screen
Total
has the following
layout:
It brings information out for:
−
Total number of disables;
−
Number of disabled zones;
−
Number of disabled
detectors;
−
Number of disabled outputs
(monitored outputs and
addressable output devices).
Mode:DAY
12:32:18
Thu 03 Feb 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Faults Total: 00000
Disables Total: 010
Failed Outputs: 00000
Disabled Outputs: 004
List/Disables/Total
TOTAL: 010
ZONES: 003
DEVICES: 003
OUTPUTS: 004
Mode:DAY
11:45:23
Thu 03 Feb 2005
FIRE CONTROL PANEL IFS7002
UniPOS
List/Disables/Total
NO DISABLES