UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
14
Revision 2.05
Of 107
The Coincidence Mode is not applicable to manual call points. If a manual call point, included in a
zone set to Coincidence Mode, responds, the fire control panel enters Fire condition, phase Fire
condition stage II in this particular zone.
Upon activation of an automatic fire detector from a zone set to Coincidence Mode, but the fire
control panel has not entered Fire condition in this zone, then:
−
If no other automatic fire detector is activated, the zone enters Pre-Fire condition;
−
If another automatic fire detector is activated, i.e. the zone is in Pre-Fire condition, then the
fire control panel enters Fire condition, phase Fire condition stage I, in this particular zone.
Exit from Pre-Fire condition in a zone is done automatically only:
−
Upon activation of a second automatic fire detector in the zone within 60 s from the Pre-Fire
condition (the fire control panel enters Fire condition, phase Fire condition stage I, in this
particular zone);
−
Upon activation of a manual call point in the zone, within 60 s from the Pre-Fire condition (the
fire control panel enters Fire condition, phase Fire condition stage II, in this particular zone)
−
Where the 60 s of Pre-Fire condition expire and neither of the above mentioned two conditions
is carried out (the first activated fire detector then receives a command to reset the fire
condition).
To set a zone in Coincidence Mode you need to appoint the parameter Coincidence Mode for this
While using the Coincidence Mode in a zone, we recommend you to include just one group of
automatic fire detectors (minimum 2 fire detectors) in this zone, allocated in one and the same room,
so upon activation of any two fire detectors you obtain a firm indication for fire in the room.
6.4. Operation of the fire control panel
When IFS7002 is switched on, reset of the system devices and initialization of the addressable
devices integrated in the loops are being done – addressable devices parameters (address,
identification number, type and class) are being verified against these saved in the energy
independent memory of the fire control panel. A text message -
System operations
- is displayed on
the LCD.
Upon completion of the system operations the fire control panel enters operation mode – it
monitors the addressable devices (automatic fire detectors, manual call points and executive devices)
by consecutively scanning their condition. Simultaneously, a constant control over the loops, the
monitored outputs and the voltage for fault conditions is being carried out.
The fire control panel IFS7002 operates in eight basic modes: Duty Mode, Fire Condition, Fault
Condition, Disabled Component Mode, Test Mode, Information and Control Mode, SetUp Mode and
Remote Control Mode.
Duty Mode, SetUp Mode and Remote Control Mode can not be combined with another mode:
−
the fire control panel enters Duty Mode after all other conditions are exited;
−
when the fire control panel enters SetUp Mode or Remote Control Mode it exits all other
conditions.
When the fire control panel is in Fire condition or in Fault condition or in a combination of one of
these, the lighting of the display is constantly on, until you press button
Stop alarm
(with the
exception of these fault conditions –
Battery low
, discharged batteries due to interruption of mains
supply, and
Fault in mains supply
). Upon
Battery low
the lighting of the display is constantly off. In all
other cases the lighting is extinguished 3 min after the last pressing of any button on the display.
Up to 250 fire alarm zones can be formed in IFS7002. Except for these zones the fire control
panel supports two additional zones:
−
Service zone (Zone 0) – here addressable devices which location in the loop can not be
detected synonymously are integrated;
−
Zone 255 – here addressable devices not included or that can not be included in a fire alarm
zone (addressable output and input devices) are integrated.
When a removed addressable device is replaced in a loop, the fire control panel runs initialization
once again and verifies its parameters (previous address, identification number, type and class)
against these saved in the energy independent memory. While this operation is being executed, the
text message
ReInitialization
appears on the display.