UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
78
Revision 2.05
Of 107
13.7.2. Function
Clean initialization
The function performs clean initialization of addressable devices in the fire alarm loops. Upon
clean initialization the addressable devices detected in the loops are being addressed consecutively,
and their parameters (ID number, type and temperature class) are being saved in the control panel.
Upon activation of the function
the following warning screen
appears:
Start the initialization via button
and in the bottom line of the panel appears the message
Wait please…
Upon unsuccessful initialization
appears the following screen:
Upon successful initialization the menu will be exited automatically.
Notes: Only swithed on loops can be initialized
Mode:DAY
15:24:47
Fri 25 Mar 2005
Initialization
Operation unsuccessful!
Would You like to run the Operation again?
–
confirm
–
cancel
Mode:DAY
15:24:21
Fri 25 Mar 2005
Initialization
Warning!
Only available Devices will be saved!
–
confirm
–
cancel