UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
49
Revision 2.05
Of 107
Simultaneously, the number in the
Go to
field will be deleted; i.e. the field is deactivated.
When you press button
the detector status is being changed alternatively from
DISABLED
to
ENABLED
and reverse; in the panel bottom left section appears a reminder
Data not saved
.
Changes (disable/enable addressable fire detector) are accepted if you press button
and the
Go to
field is empty – then the reminder
Data not saved
disappears.
12.3.1.3. Menu
Outputs
The menu is used for disabling and enabling outputs (monitored outputs and addressable output
modules. It contains the following subordinate menu and functions:
−
Monitored outputs;
−
Addr Outputs Loop1;
−
Addr Outputs Loop 2.
Upon activation of function
Monitored outputs
a screen
displaying the status of the control
panel’s monitored outputs appears:
Buttons
and
appearing
in the right panel section allow the
user to switch between the first and
the second monitored output.
When you press button
the monitored output status is being
changed alternatively from
DISABLED
to
ENABLED
and
reverse; in the panel bottom left
section appears a reminder
Data not
saved
. Changes (disable/enable
addressable monitored output) are
accepted if you press button
and the
Go to
field is empty – then the reminder
Data not saved
disappears.
Menus
Addr Outputs Loop1
and
Addr Ouputs Loop 2
have identical layout. Enter the menus to
display one of the following screens:
−
If no disabled addressable
output modules are available:
Mode:DAY
15:09:10
Mon 21 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
System functions/Disables/Outputs
Go to:
Disabled Outputs - total Loop1 000
Loop 1
OUTPUT:
0
1
2
3
4
5
6
7
8
9
С
Mode:DAY
14:39:46
Mon 21 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Faults total: 00000
Disables total: 003
Failed Outputs: 00000
Disabled Outputs: 001
System functions/Disables/Outputs
Monitored output 1:
DISABLEDDISABLED
Monitored output 2:
ENABLED