UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
84
Revision 2.05
Of 107
13.8.3. Menu
Addressable outputs
Use the menu to check the addressable outputs of the control panel.
When you enter the menu the following operations are being run:
−
If no addressable outputs are available – a screen with the message
No addressable outputs
appears; the only option is to exit the menu;
−
If some addressable outputs
are available – a command
for activation is sent to the
first addressable output, if the
loop is On and is initialized. A
screen for the output status
and for selection of the next
output for check up is
visualized:
For the current addressable
output is displayed:
−
The loop it is included in, its
address in the loop and the
number of the output in the
device, if more than one
output is available;
−
Device text message;
−
Device status (
On
or
Off
) – it
is displayed only when the loop the device is included in is On and is initialized;
−
Information for the communication with the device:
♦
the loop is off – appears the message
The loop is off
(no attempt for communication
with the device has been made);
♦
the loop is On, but is not initialized – appears the message
Uninitialized loop
(no
attempt for communication with the device has been made);
♦
the loop is On and is initialized – as a result from communication with the device
(
Successful data transfer to the device
or
Error in data transfer to the device
).
The current addressable output is pointed by arrow – „
>>
”.
When the data transfer is successful the device output will be activated.
Buttons
and
in the right panel section are visualized if more than one addressable output
is available; the
Go to
field in the heading and the digit buttons appear if addressable outputs in more
than one device are available.
When you press a digit button the
Go to
field is activated; you can enter a random 3-digit number
for the device. To edit the number use button
press it to delete the last entered digit.
The devices obtain numbers according to the following sequence: from the first device in Loop 1
to the last device in Loop 1; from the first device in Loop 2 to the last device in Loop 2.
When you press button
and a number is already entered in the
Go to
field, the first
addressable output in the first device whose number is equal to or higher than the number in the field
will be selected:
−
if the number is 0, the first addressable output will be selected;
−
if the number is higher than the number of device having the last addressable output, the last
addressable output will be selected.
At the same time:
−
the number in the
Go to
field is deleted, i.e. the field is deactivated;
−
the output that has been checked receives a command to switch off, if the loop is On and is
initialized;
−
the output that has been selected for check-up, receives a command for activation, if the loop
is On and is initialized;
Mode:DAY
14:43:46
Mon 28 Mar 2005
Check addressable Outputs
Go to:
Activated Device:
>>
Lp1
А
ddr25.1
Point 1.025
Device is On
Successful data Transfer to the Device
0
1
2
3
4
5
6
7
8
9
С
С