UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
81
Revision 2.05
Of 107
When you press a digit button, the
Go to
field is activated and you can enter a random 3-digit
number for the device. To edit the number, press button
and the last entered digit will be deleted.
When you press button
and a number is already entered in the
Go to
field, the device
whose number is in the field will be selected:
−
If the number is 0, Address 1 in Loop 1 will be selected ;
−
If the number is higher than 250, Address 125 in Loop 2 will be selected.
Simultaneously, the number in the
Go to
field is deleted, i.e. the field is deactivated.
When you press button
and a number is entered in the
Go to
field, the field will be
deactivated.
When you press button
and the
Go to
field is empty, a screen
for exclusion/inclusion of the
addressable device appears:
The status of the device is
displayed in inversive colours.
Change the status by pressing button
– the status is changed
alternatively from
included
to
excluded
and vice versa.
13.7.5. Menu
Check
The menu is provided for check up of the initialization of addressable devices, included in the fire
alarm loops.
When you enter the menu the following operations are being run:
−
If no devices are available in the loops – a screen with the message
No devices
appears; the
only option is to exit the menu;
−
If some devices are available
in the loops – a command for
LEDs illumination is sent to
the first device, if the loops
are On and are initialized. A
screen for the device status
and for selection of the next
device for check up is
visualized:
For the current device is displayed:
−
The loop it is included in, and its address in the loop;
−
Its text message;
Mode:DAY
10:33:39
Mon 28 Mar 2005
Check
Devices Total: 63
Go to:
Indicated Device:
>>
Lp1
А
ddr1
Point 1.001
Device is On
Successful data Transfer to the Device
0
1
2
3
4
5
6
7
8
9
d
Mode:DAY
10:08:31
Mon 28 Mar 2005
Exclude Devices
Lp1
А
ddr1
On
Point 1.001
С