13.7.1. Function
Initialization
The function performs standard initialization of the addressable devices in the fire alarm loops.
During the operation addressable devices parameters (address, ID number, type and temperature
class) are checked against these saved in the memory of the control panel.
Upon activation of the function
the following warning screen
appears:
Start the initialization via button
and in the bottom line of the panel appears the message
Wait please
...
Upon unsuccessful initialization
appears the following screen:
Upon successful initialization the menu will be exited automatically.
Notes:
1. Only swithed on loops can be initialized.
2. The function is not affected by removed addressable devices, i.e. the opretaion will be
successful even when some devices are removed from the loops.
Mode:DAY
13:37:24
Fri 25 Mar 2005
Initialization
Operation unsuccessful!
Would You like to run the Operation again?
–
confirm
–
cancel
Mode:DAY
13:30:51
Fri 25 Mar 2005
Initialization
Warning!
New Initialization!
–
confirm
–
cancel