UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
34
Revision 2.05
Of 107
The screen
Panel Outputs
provides information for outputs
responding to the relevant phase of
Fire condition in the zone:
The screen
List of addressable
outputs
displays information for
addressable outputs associated to
the zone. If no such outputs are
available, a screen displaying the
message
No addressable outputs
activated upon Fire condition Phase
X
appears. (X stands for the phase
number – 1 or 2). The only option
then is to exit the screen. If
addressable outputs associated to
the zone are available, their list is
visualized. Loop number, device
address in the loop and the number
of the output in the device, if more
than one is displayed for each
device. The list is visualized in
pages, each page containing a
maximum of 10 devices. The buttons
and
on the right panel section appear where more than one page is available and allow the
user to switch between next and previous page.
Mode:DAY
12:23:45
Sat 12 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Parameters: Zone 1
Fire Phase 2 Outputs
List of addressable Outputs Total: 10
Loop1 Addr7.2 Loop1
А
ddr8
Loop1
А
ddr7.3 Loop2
А
ddr9
Loop1
А
ddr7.4 Loop2
А
ddr10.1
Loop1
А
ddr7.5 Loo
р
2
А
ddr11.1
Loop1
А
ddr7.6 Loop2
А
ddr12
Mode:DAY
11:29:21
Sat 12 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Parameters: Zone 1
Fire Phase 1 Outputs
Panel Outputs
Monitored Output 1
No
Monitored Output 2
No
Relay
Output
Yes