UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
65
Revision 2.05
Of 107
13.5.2. Menus
Fire Phase 1 Outputs
and
Fire Phase 2 Outputs
The menus alow the user to associate outputs to the zone, that wil be triggered in fire condition
(phase Fire condition stage I and phase Fire condition stage II). The menus contain:
−
Menu
Panel Outputs
−
Screen
List of addressable outputs
;
−
Menu
Remove addressable output;
−
Menu
Add addressable output
.
If no associated addressable outputs are available, menu
Remove addressable output
is not
accessible. If 30 addressable outputs are associated to the zone, menu
Add addressable output
is
not accessible.
13.5.2.1. Menu
Panel Outputs
Menu
Panel Outputs
allows the
user to associate control panel
outputs to the zone, in accordance
with the Fire phase:
To edit the parameters use
button
– press it to
alternatively change the value of the
current parameter to
Yes
(the output
will be activated upon relevant phase
of Fire condition in the zone) and to
No
(the output will remain inactive
upon relevant phase of Fire condition
in the zone) and vice versa.
13.5.2.2. Screen
List of addressable outputs
The screen displays a list of
addressable outputs, associated to
the zone. For each output is
displayed the loop where the output
module is included in, its address in
the loop and the number of the
output in the module, if more than
one.
If no addressableoutputs are associated to the zone, a screen with the message
No addressable
outputs activated upon Fire Condition Phase X
(X stands for phase number – 1 or 2)
Mode: DAY
12:38:51
Thu 24 Mar 2005
SetUp Zone 1
Fire Phase 1 Outputs
List of addressable Outputs Total: 11
Loop 1
А
ddr 7.2 Loop 2
А
ddr 13.2
Loop 1
А
ddr 7.3
Loop 1
А
ddr 7.4
Loop 1
А
ddr 7.5
Loop 1
А
ddr 7.6
Loop 1
А
ddr 8
Loop 2
А
ddr 9
Loop 2
А
ddr 10.1
Loop 2
А
ddr 11.1
Loop 2
А
ddr 12
Mode: DAY
11:53:31
Thu 24 Mar 2005
SetUp Zone 1
Fire Phase 1 Outputs
Panel Outputs
Monitored Output 1
No
Monitored Output 2
No
Relay
Output
Yes