- 42 -
14.Linearization function
The output (indicated value) set up to the input set up arbitrarily is carried out.
An input and output can carryout a 21-channel (ch) setup of the setup.
≪Linearization function≫
[Use of a linearization function]
The use of a linearization function should choose“1:Linearization operation”by
“Calculation function”of the mode No.0
[Input % value setup]
It sets up at a rate(%)of a full-scale input.
There are kinds of setting methods. Key operation and the teaching function to take in an
analog input signal directly. A setting range is 0.00 to 105.00%.
Table 7
Form
0.00%
to
100.00%
to
105.00%
A2
4.000mA
to
20.000mA
to
20.800mA
A3
1.000V
to
5.000V
to
5.200V
A4
0.000V
to
5.000V
to
5.250V
A5
0.000V
to
10.000V
to
10.500V
<Caution>
1. While using key operation, it can change into the value of 105.00% or more, but shift to the
next ch and registration cannot beperformed. Please be sure to set up with less than
105.00% values.
2. When a teaching function is operated at less than 0.00% and 105.00% or more at the time
of use, it becomes registration at the minimum and the maximum.
3. By ch, when an input % value setup is the same, output indicated value setup of a front row
ch setup becomes effective.
(Example:When ch03,11 and 19 are the same, an output indicated value setup of ch03 is
effective.)
4. An input % value setup “000.00”is input data of 0%、and is not ch skip setup.
A setup of at least one “000.00”setup will operate linearization between 0% and the
latest input % value setup.
When linearization wants to function, without going via 0% of input %setup, it has inputt
ed except 0%, and also please input an input value setup which overlapped with ch.
(Keep in mind that an output indicated value setup in the front row ch becomes effective.)
[Output indicated value setup]
It sets up with an indicated value.(Key operation input)
Setting range, -9999 to 9999(A decimal point is interlocked with mode No.0)
≪How to call≫
1.It will become” “ displays if a is pressed 2 sec or more.(Setting list)
2.Please push a 3 times and make it “ “display.
3.If a is pressed, it will become a Rinaraizu setup and can perform a setup of ch1 to ch21.
Mode
Mode
!
Summary of Contents for LV1000 Series
Page 16: ...12 The setting menu Each mode transition Preset value setting...
Page 17: ...13 Mode setting Scaling setting...
Page 18: ...14 Linearization setting 8 step preset value setting...
Page 19: ...15 Test mode...
Page 57: ...53 Analog adjustment mode flow chart...
Page 64: ...60 Dimensions Fig 26...