16.The method of analog adjustment
<Caution>
Although adjusting according to a visitor`sspecification, when you carry out analog adjustment,
please chang according to the following procedure.
≪The call method≫
1.Power is switched on pushing , It becomes the 「A2 to A5 」display.(Analog adjustment mode)
≪The key operation method of analog adjustment≫
Operating key
Display unit
Operation procedure
A B C D E
A 2
1 2 3 4
○ ○ ○ ○
Hold %
○ ○
A2 to A5 input range is switched whenever it presses a
┌ →A2→A3→・・・・→A5→ ┐
└────────────────┘
Please choose the input range which suited specification.
A2
DC4 to 20mA input
A3
DC1 to 5V input
A4
DC0 to 5V input
A5
DC0 to 10V input
A B C D E
A 5
1 2 3 4
○ ○ ○ ○
Hold %
○ ○
When pushed, will register the input range currently
displayed.
When a range is made, a scaling preset value initializes.
A B C D E
A.0 1 2 3
1 2 3 4(bit-data)
○ ○ ○ ○
Hold %
○ ○
When pushed, it becomes the analog minimum input value
adjustment.
The input value (bit-data) inputted now is displayed.
A B C D E
A.
0
1
2
3
During registration, it
blinks 3 times.
1 2 3 4
○ ○ ○ ○
Hold %
○ ○
If a is pressed inputting the minimum of the
registered input range, the input value (bit-data) in the
time will be registered as a minimum input.
As a signal registration, bit-data blink 3 times in about
1 sec.
<Caution>
Key operation cannot be carried out during bit-data
registration.
A B C D E
A.0 1 2 3.
Lighting
1 2 3 4
◎ ○ ○ ○
Hold %
○ ○
When registered bit-data is checked,
It displays, while pressing the .
※When displaying bit-data registered,
The decimal point of a least significant digit lights up.
RST
Mode
Mode
ENT
ENT
Mode
Mode
!
!
Summary of Contents for LV1000 Series
Page 16: ...12 The setting menu Each mode transition Preset value setting...
Page 17: ...13 Mode setting Scaling setting...
Page 18: ...14 Linearization setting 8 step preset value setting...
Page 19: ...15 Test mode...
Page 57: ...53 Analog adjustment mode flow chart...
Page 64: ...60 Dimensions Fig 26...