- 30 -
Mode No. Setting the zero point adjustment and auxiliary input
3
A B C D E
3.0 0
Auxiliary input
0:Peak hold
1:Bottom hold
2:Hold
3:Input WIDTH tag
4:0 compulsion functions
0 point adjustment
0:0 point adjustment invalidity・Clearness
1:0 point adjustment is effective
2:0 point adjustment invalidity
[ Auxiliary input ]
The function when terminal stand no 6 and 7 are on is set.
These functions of a Rate meter/Ratio are effective.
The Hdlamp is on when an external input terminal is ON.
0:Peak hold 〔While functioning、an indicated value lights up.〕
The maximum value between those is displayed while an external input
terminal has been turned on.
It returns to the measurement indication when turning it off.
1:Bottom hold 〔While functioning、an indicated value lights up.〕
The minimum value between those is displayed while an external input
terminal has been turned on.
It returns to the measurement indication when turning it off.
2:Hold 〔While functioning、an indicated value lights up.〕
The indicated value when turning it on is maintained while an external
input terminal has been turned on.
It returns to the measurement indication when turning it off.
3:Input width indication 〔While functioning、an indicated value lights up.〕
When an external input terminal has been in ON state,
”maximum indicated value - minimum indicated value” is indicated.
It returns to the measurement indication when turning it off.
For instance, While the external input terminal has been in ON state, when the maximum
is 600 and the minimum is 100, it is set to “600-100”and“500”is indicated.
4:0 compulsion functions 〔While functioning、an indicated value lights up.〕
If an external input terminal is turned on, the indication at that time
becomes"0"
The indicated valu of the functional adds and indicated a part for a deviation.
It returns to the measurement indication when turning it off.
For instance,when it is "5V" and the indication is "5000",a present input when an
external input terminal is turned on,that indication scales,and indication the
measurement value as "input is "5V" = indication is "0"".
<Caution>
1.About the preset output/8 step preset output function, a judgment output is
carried out to the resultof an internal measurement value.
About the analog output function, output selection is possible by setup of
mode №A“output system”
2.The indicated value function is updated synchronizing with the mode №2“
sampling time.”(A hold is excluded.)
!
Summary of Contents for LV1000 Series
Page 16: ...12 The setting menu Each mode transition Preset value setting...
Page 17: ...13 Mode setting Scaling setting...
Page 18: ...14 Linearization setting 8 step preset value setting...
Page 19: ...15 Test mode...
Page 57: ...53 Analog adjustment mode flow chart...
Page 64: ...60 Dimensions Fig 26...