- 21 -
10.Scaling setting method
≪The call method≫
1.It will became「 」display if“ “is pushed 2 sec or more.(Set list)
2.It will became「 」display if“ “is pushed twice.
3.If“ “is pushed,it will become a scaling setup and can perform a setup of an input
indicated value and an output indicated value.
≪Programming and information lamp operation≫
№
Set item
Set content
Information
Lamp operation
① Minimum value.
The minimum indicated value of set.
OUT1 light
② Minimum analog input value.
The analog input value to a minimum indicated
is set. *1
OUT1 blinking
③ Maximum value.
The maximum indicated value of set.
OUT2 light
④ Maximum analog input value.
The analog input value to a maximum indicated
is set. *1
OUT2 blinking
⑤
The indicated value at moment
0.0 %
The rate mete indicated value when ratio 0.0%
is set.
% light
⑥
The indicated value at moment
100.0 %
The rate mete indicated value when ratio
100.0% is set.
% blinking
⑦
Domain 0 minimum indicated
value.
The minimum indicated value of domain 0 is
set.*2
OUT3 light
⑧
Domain 0 maximum indicated
value.
The maximum indicated value of domain 0 is
set.*2
OUT3 blinking
⑨ Analog output minimum value.
The indicated value when analog minimum
outputting is set.
OUT4 Light
⑩ Analog output maximum value.
The indicated value when analog maximum
outputting is set.
OUT4 blinking
※1 If a (First push)+ is preseesd when setting up an input value, the analog value
inputted now will be rewritten by the settin up value.
※2 Please set up on condition of the“domain 0 minimum indicated value<domain 0 maximum
indicated value”
※3 When you use a linearization function, ①-④ will not work.
【Rate meter:№①-④】
When linearization measurement is invalid, It scaling it setting the minimum value, the maximum
value, and the analog input value to it by the straight line that connects between two points.
linearization measurement measures by linearization setup at the time of effective.
The minimum / the maximum indicated value.
Setting range:A2 to A5 type -9999 to 9999.(The decimal point synchronizes with in mode №0.)
Analog input value of the minimum / the maximum indication.
Setting range: A2 type: 4.00 to 20.00(mA) A5 type: 0.00 to 10.00(V)
A3 type: 1.00 to 5.00(V)
A4 type: 0.00 to 5.00(V)
<Caution>
1. When setting as <minimum indication value = maximum indication value >, the indication
doesn`t change.
2. The minimum / the maximum analog input value should not carry out a setup outside a setting
range.
3. Please do not carry out a setup of those other than
”the minimum analog setting value”< ”the maximum analog setting value”.
Mode
Mode
!
Summary of Contents for LV1000 Series
Page 16: ...12 The setting menu Each mode transition Preset value setting...
Page 17: ...13 Mode setting Scaling setting...
Page 18: ...14 Linearization setting 8 step preset value setting...
Page 19: ...15 Test mode...
Page 57: ...53 Analog adjustment mode flow chart...
Page 64: ...60 Dimensions Fig 26...