Electrical connection
52
5816,0013US / Version 02
8.4.3
Connecting testable safety devices and test them
Connect the connection lines of the testable safety device to
clamps X11 and X20.
By default, MAGNETIC installs a jumper between terminals X11
OUT and IN. When a testable safety device is connected, the
jumper must be removed.
See page 91, chapter 16.1 "Wiring diagrams".
8.4.4
Connecting emergency opening contacts
Fire-fighter switch, emergency opening contacts, etc. are
connected to the "Open high priority" input. When the signal is
applied to this input, the barrier opens. While the signal is present,
the barrier cannot be closed.
See page 91, chapter 16.1 "Wiring diagrams".
8.4.5
Digital inputs
Technical data
NOTE!
The digital input functions can be freely
parameterised.
For input parameterisation, see
separate document "Description of control units
MGC and MGC Pro for MHTM
TM
MicroDrive
barriers".
Factory setting
Clamp
Description
Function
IN1
Input 1
Open low priority
IN2
Input 2
Open low priority
IN3
Input 3
Open high priority
IN4
Input 4
Open Service
IN5
Input 5
Close Service
IN6
Input
6
Close
IN7
Input
7
Close
IN8
Input 8
Blink signal light
Table 8: Factory settings "Digital inputs"