G7 ASD Operation Manual
67
Preset Speed #3
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
3
This parameter assigns an output frequency to binary number 0011 and is
identified as Preset Speed #3. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018
for further
information on this parameter).
Direct Access Number — F020
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
F013
)
Maximum — Upper Limit (
F012
)
Units — Hz
Preset Speed #4
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
4
This parameter assigns an output frequency to binary number 0100 and is
identified as Preset Speed #4. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018
for further
information on this parameter).
Direct Access Number — F021
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
F013
)
Maximum — Upper Limit (
F012
)
Units — Hz
Preset Speed #5
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
5
This parameter assigns an output frequency to binary number 0101 and is
identified as Preset Speed #5. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018
for further
information on this parameter).
Direct Access Number — F022
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
F013
)
Maximum — Upper Limit (
F012
)
Units — Hz
Preset Speed #6
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
6
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Speed #6. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018
for further
information on this parameter).
Direct Access Number — F023
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
F013
)
Maximum — Upper Limit (
F012
)
Units — Hz
Preset Speed #7
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
7
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Speed #7. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018
for further
information on this parameter).
Direct Access Number — F024
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
F013
)
Maximum — Upper Limit (
F012
)
Units — Hz
Low Speed Signal Output Frequency
Program
⇒
Terminal Selection Parameters
⇒
Reach Settings
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal so long as the ASD output
is at or above this setting (see
Table 9 on pg. 81
for the available output
assignments).
Direct Access Number — F100
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (
F011
)
Units — Hz