G7 ASD Operation Manual
165
Accel/Decel Special Display Resolution
Program
⇒
Special Control Parameters
⇒
Accel/Decel Special
This parameter sets the number of decimal places to be displayed for Accel/
Decel functions.
Direct Access Number — F704
Parameter Type — Numerical
Factory Default — 0.1
Changeable During Run — Yes
Minimum — 1
Maximum — 0.01
Prohibit Initializing User Parameters During Typeform
Initialization
Program
⇒
Special Control Parameters
⇒
Special Parameters
⇒
Prohibit Initializing User Parameters During Typeform Initialization
This parameter Enables/Disables the ability to initialize user parameters during
a Type Form initialization.
Settings:
Allowed
Prohibited
Direct Access Number — F709
Parameter Type — Selection List
Factory Default — Allowed
Changeable During Run — Yes
V/f Group
No path available (Direct Access Only)
While operating using the LED Keypad Option 1 of 4 V/f groups may be
selected and run. Each V/f group is comprised of 4 user-defined variables: Base
Frequency, Base Frequency Voltage, Manual Torque Boost, and Electronic
Thermal Protection. Expanded descriptions of these parameters may be found
in this section (
Direct Access Parameter Information
).
Settings:
Group 1
Group 2
Group 3
Group 4
Note:
If using the LCD EOI, press ESC from the Frequency
Command screen to access this parameter.
Direct Access Number — F720
Parameter Type — Selection List
Factory Default — 1
Changeable During Run — Yes
Stop Pattern
No path available (Direct Access Only)
While operating using the LED Keypad Option the Stop Pattern parameter
determines the method used to stop the motor when the stop command is issued
via a Stop command from the LED Keypad.
The Decel Stop setting enables the Dynamic Braking system that is setup at
F304
or the DC Injection Braking system that is setup at
F250
,
F251
, and
F252
.
The Coast Stop setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
Decel Stop
Coast Stop
Note:
The Stop Pattern setting has no effect on the Emergency Off
settings of
F603
. If using the LCD EOI, press ESC from the
Frequency Command screen to access this parameter.
Direct Access Number — F721
Parameter Type — Selection List
Factory Default — Decel Stop
Changeable During Run — Yes
F704
F721