G7 ASD Operation Manual
Accel #2 Time
Program
⇒
Special Control Parameters
⇒
#1 – #4 Settings
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to
the Maximum Frequency for the #2 Acceleration profile. The accel/decel
pattern may be set using
F502
. The minimum accel/decel time may be set using
F508
.
This setting is also used to determine the acceleration rate of the Motorized Pot
function.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.
Direct Access Number — F500
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Decel #2 Time
Program
⇒
Special Control Parameters
⇒
Accel/Decel #1 – #4
Settings
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The accel/
decel pattern may be set using
F502
. The minimum accel/decel time may be set
using
F508
.
This setting is also used to determine the deceleration rate of the Motorized
Pot function.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.
Direct Access Number — F501
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds