130
G7 ASD Operation Manual
Synchronized Torque Bias Input
Program
⇒
Torque Setting Parameters
⇒
Torque Control
This parameter Enables/Disables the Synchronized Torque Bias input
function. When enabled, this parameter identifies the source of the
Synchronized Torque Bias input signal.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
LED Keypad Option
Binary/BCD Input
Common Serial (TTL)
RS232/RS485
Communication Card
Direct Access Number — F422
Parameter Type — Selection list
Factory Default — Disabled
Changeable During Run — Yes
Tension Torque Bias Input
Program
⇒
Torque Setting Parameters
⇒
Torque Control
This parameter Enables/Disables the Tension Torque Bias input function and
identifies the source of the Tension Torque Bias input signal when enabled.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
LED Keypad Option
Binary/BCD Input
Common Serial (TTL)
RS232/RS485
Communication Card
Direct Access Number — F423
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Load Sharing Gain Input
Program
⇒
Torque Setting Parameters
⇒
Torque Control
This parameter Enables/Disables the Load Sharing Gain input function and is
enabled by selecting a Load Sharing Gain input signal source.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
LED Keypad Option
Binary/BCD Input
Common Serial (TTL)
RS232/RS485
Communication Card
Direct Access Number — F424
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F422
F424