G7 ASD Operation Manual
109
Jump Frequency #3
Program
⇒
Special Control Parameters
⇒
Jump Frequencies
Same as Jump Frequency #1
(
F270
) and is used when multiple frequencies
are to be jumped (see the plus-or-minus value setting at
F275
). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
Jump Frequency #3 Bandwidth
Program
⇒
Special Control Parameters
⇒
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(
F274
).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency Processing
Program
⇒
Special Control Parameters
⇒
Jump Frequencies
⇒
Jump
Frequency Processing
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See
F270
for further information on the Jump Frequency settings.
Settings:
Process Amount (use PID feedback)
Output Frequency
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Yes
Preset Speed #8
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
8
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018
for further
information on this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit (
F013
)
Maximum — Upper Limit (
F012
)
Units — Hz
Preset Speed #9
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
9
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed #9. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018
for further
information on this parameter).
Direct Access Number — F288
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
F013
)
Maximum — Upper Limit (
F012
)
Units — Hz
F274
F288