G7 ASD Operation Manual
35
Frequency Control
Selections
The following is a listing and description of the
Frequency Mode (
F003
) selections (Program
⇒
Fundamental Parameters
⇒
Standard Mode Selection
⇒
Frequency Mode #1).
Settings:
Use VI/II
0 to 10-volt DC analog input connected to VI or a
4 – 20 mA (or 0 to 1 mA) DC current connected to
II (cannot use both simultaneously).
Use RR
0 to 10-volt DC analog input connected to RR.
Use RX
-10 to +10-volt DC analog input connected to RX.
Use Option Card RX2
-10 to +10-volt DC analog input connected to RX2.
Use LED Keypad Option
The LED Keypad is unavailable at the time of this release.
Use Binary/BCD Input
Allows for discrete terminal input to control the ASD output.
Use Common Serial (TTL)
To use the EOI for control requires that the LCD Port Connection be set to Common Serial
(TTL) to use this feature.
Use RS232/RS485
To use the EOI for control requires that the LCD Port Connection be set to RS232/RS485 to use
this feature.
Use Communication Card
Routes the control and monitoring I/O to CNU3 of the Control Board of the G7 ASD (Option
Card connector).
Use Motorized Pot Simulation
A discrete terminal may be configured to increase or decrease the speed of the motor by
momentarily connecting the assigned terminal to CC. See
Table 8 on page 76
for further
information on this feature.
Use Pulse Input Option
Configures the system to receive pulse input. See PG Speed Reference Setpoint on
pg. 103
for
further information on this feature.