G7 ASD Operation Manual
169
RS232/RS485 Communications Time-Out Action
Program
⇒
Communication Setting Parameters
⇒
Communication
Settings
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out
Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the drive.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
No Action
Alarm
Trip
Direct Access Number — F804
Parameter Type — Selection List
Factory Default — Trip
Changeable During Run — Yes
Communication Interval
Program
⇒
Communication Setting Parameters
⇒
Communication
Settings
This parameter sets the Common Serial response delay time.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F805
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
TTL Master Output
Program
⇒
Communication Setting Parameters
⇒
Communication
Settings
In a master/follower configuration, this setting determines the output parameter
of the master ASD that will be used to control the applicable follower ASDs.
Note:
Select No Follower if
F826
is configured as a Master Output
controller. Otherwise, an EOI failure will result.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
No Follower (normal operation)
Frequency Reference
Output Command Frequency
Torque Command
Output Torque Command
Direct Access Number — F806
Parameter Type — Selection List
Factory Default — No Follower (normal
operation)
Changeable During Run — Yes
F804
F806