44
G7 ASD Operation Manual
Panel Menu
The Panel menu may be accessed in either of two ways: while operating using the LED Keypad Option
the Panel menu may be accessed via
F008
or if operating in the Local mode using the LCD EOI, press
ESC from the Frequency Command screen.
The control settings of the Panel menu are effective for LED keypad control only if accessed via Direct
Access method
F008
and are effective for the LCD EOI control only if accessed via the Frequency
Command screen. Changes made to either of the Panel menus are not carried over to the other Panel
menu.
Using either method provides quick access to the following Panel menu parameters:
Direction — Forward or Reverse (see
F008
for further information on this setting).
Stop Pattern — The Decel Stop or Coast Stop settings determines the method used to stop the motor
when using the Stop|Reset key of the EOI. The Decel Stop setting enables the Dynamic Braking
system setup at
F304
or the DC Injection Braking system setup at
F250
,
F251
, and
F252
. The Coast
Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Note:
The Stop Pattern setting has no effect on the Emergency Off settings of
F603
.
V/f Group — 1 of 4 V/f profiles may be selected and run. Each V/f profile is comprised of 4 user
settings: Base Frequency, Base Frequency Voltage, Manual Torque Boost, and Electronic
Thermal Protection. Expanded descriptions of these parameters may be found in the section titled
Direct Access Parameter Information on pg. 59
.
Accel/Decel Group — 1 of 4 Accel/Decel profiles may be selected and run. Each of the Accel/Decel
profiles is comprised of 3 user settings: Acceleration, Deceleration, and Pattern. Expanded
descriptions of these parameters may be found in the section titled
Direct Access Parameter
Information on pg. 59
(or see
F009
).
Feedback in Panel Mode — This feature enables or disables the PID feedback function.
Torque Limit Group — This parameter is used to select 1 of 4 preset positive torque limits to apply
to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be setup at
F441
,
F444
,
F446
, and
F448
, respectively.