100
G7 ASD Operation Manual
RX2 Speed Reference Setpoint #2 (%)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control or the Torque Control mode.
See
F222
for further information on this setting.
This parameter sets the RX2 input level that represents RX2 Reference
Setpoint #2 (frequency) (direction/torque/frequency). This value is entered as
-100 to +100% of the -10 to +10 VDC RX2 input signal range.
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
RX2 Speed Reference Setpoint #2 (frequency)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control mode.
See
F222
for further information on this setting.
This parameter sets RX2 Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of
F224
.
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
RX2 Torque Reference Setpoint #1 (%)
Program
⇒
Torque Setting Parameters
⇒
Setpoints
⇒
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX2 input level and motor load.
See
F222
for further information on this setting.
This parameter sets RX2 Torque Reference Setpoint #1 (%) and is the output
torque value that is associated with the setting of
F222
. This value is entered as
-250 to +250% of the rated torque.
Direct Access Number — F226
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
RX2 Torque Reference Setpoint #2 (%)
Program
⇒
Torque Setting Parameters
⇒
Setpoints
⇒
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX2 input level and motor load.
See
F222
for further information on this setting.
This parameter sets RX2 Torque Reference Setpoint #2 (%) and is the output
torque value that is associated with the setting of
F224
. This value is entered as
-250 to +250% of the rated torque.
Direct Access Number — F227
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
F224
F227