G7 ASD Operation Manual
RR Speed Reference Setpoint #2 (%)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
See
F210
for further information on this setting.
This parameter sets the RR input level that represents RR Reference Setpoint
#2 (frequency) (torque or frequency). This value is entered as 0 – 100% of the
0 – 10 VDC RR input signal range.
Direct Access Number — F212
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
RR Speed Reference Setpoint #2 (frequency)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control
mode.
See
F210
for further information on this setting.
This parameter sets RR Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of
F212
.
Direct Access Number — F213
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Hz
RR Torque Reference Setpoint #1 (%)
Program
⇒
Torque Setting Parameters
⇒
Setpoints
⇒
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Torque Control
mode.
This is accomplished by establishing an associated V/f output pattern for a given
RR input level and motor load.
See
F210
for further information on this setting.
This parameter sets RR Torque Reference Setpoint #1 and is the output torque
value that is associated with setting of
F210
. This value is entered as 0 – 250%
of the rated torque.
Direct Access Number — F214
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
RR Torque Reference Setpoint #2 (%)
Program
⇒
Torque Setting Parameters
⇒
Setpoints
⇒
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Torque Control
mode.
This is accomplished by establishing an associated V/f output pattern for a given
RR input level and motor load.
See
F210
for further information on this setting.
This parameter sets RR Torque Reference Setpoint #2 and is the output torque
value that is associated with setting of
F212
. This value is entered as 0 – 250%
of the rated torque.
Direct Access Number — F215
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %