Electronic Gear Setting
Program
⇒
Feedback Parameters
⇒
PG Settings
This parameter sets the number of pulses per revolution when using a shaft-
mounted encoder and the PG Option Board for closed loop speed control.
Direct Access Number — F370
Parameter Type — Numerical
Factory Default — 1000
Changeable During Run — No
Minimum — 100
Maximum — 4000
Position Loop Gain
Program
⇒
Feedback Parameters
⇒
PG Settings
This parameter provides a divisor for the pulse input when operating in the
Pulse Control mode.
Direct Access Number — F371
Parameter Type — Numerical
Factory Default — 4.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Position Completion Range
Program
⇒
Feedback Parameters
⇒
PG Settings
During a deceleration ramp, this parameter sets a speed range that must be
attained before the Stop command may be executed.
Direct Access Number — F372
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 1
Maximum — 4000
Frequency Limit at Position
Program
⇒
Feedback Parameters
⇒
PG Settings
While operating in the Position-Control mode and using PG feedback, this
setting determines the maximum acceleration rate in Hz/second.
Direct Access Number — F373
Parameter Type — Numerical
Factory Default — 800
Changeable During Run — Yes
Minimum — 1
Maximum — 8001
Units — Hz/Second
Current Control Proportional Gain
Program
⇒
Feedback Parameters
⇒
PG Settings
This parameter sets the sensitivity of the drive when monitoring the output
current to control speed. The larger the value entered here, the more sensitive
the drive is to changes in the received feedback.
Direct Access Number — F374
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 100.0
Maximum — 1000