G7 ASD Operation Manual
103
BIN Torque Reference Setpoint #2 (%)
Program
⇒
Torque Setting Parameters
⇒
Setpoints
⇒
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input and motor load.
See
F232
for further information on this setting.
This parameter sets BIN Torque Reference Setpoint #2 (%) and is entered as
-250 to +250% of the rated torque.
Direct Access Number — F233
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
PG Speed Reference Setpoint #1 (%)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
PG
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction control input. The PG input
signal is a pulse count originating from a shaft-mounted Encoder.
Note:
The PG input terminal may be used with the ASD-Multicom
option board only.
Perform the following setup to allow the system to receive a binary control
input:
•
Program
⇒
Fundamental Parameters
⇒
Standard Mode Selection
⇒
Command Mode
⇒
(
any setting).
•
Program
⇒
Fundamental Parameters
⇒
Standard Mode Selection
⇒
Frequency Mode #1
⇒
Use Pulse Input Option.
•
Provide a Run command (F or R).
The settings that determine the direction, gain, and bias of the PG input are:
•
PG Speed Reference Setpoint #1 (frequency)
(
F235
)
,
•
the PG input pulse count that represents PG Speed Reference
Setpoint #1 (frequency):
F234
,
•
PG Speed Reference Setpoint #2 (frequency)
(
F237
)
, and
•
the PG input pulse count that represents PG Speed Reference
Setpoint #2 (frequency):
F236
.
Once set, as the PG input pulse count changes, the directional information or
the output frequency of the drive will vary in accordance with the above
settings.
This parameter sets the PG input pulse count that represents Reference
Setpoint #1 (frequency) (direction/speed). The range of values for this
parameter is -100 to +100% of the PG input pulse count range.
Note:
Further application-specific PG settings may be performed from
the following path: Program
⇒
Feedback Parameters
⇒
PG
Settings
.
Direct Access Number — F234
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
Frequency Settings
F233