G7 ASD Operation Manual
133
Power Running Torque Limit #1
Program
⇒
Torque Setting Parameters
⇒
Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting. If Setting is selected, the value set at
F441
is used as the
Power Running Torque Limit #1 input.
Settings:
VI/II
RR
RX
RX2 (option)
Setting
Direct Access Number — F440
Parameter Type — Selection List
Factory Default — Setting
Changeable During Run — Yes
Driving Torque Limit #1
Program
⇒
Torque Setting Parameters
⇒
Manual Torque Limit
Settings
This parameter provides a value for the Power Running Torque Limit #1
setting if Setting is selected at
F440
. This value provides the positive torque
upper limit for the #1 motor.
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Regeneration Torque Limit #1
Program
⇒
Torque Setting Parameters
⇒
Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal. If Setting is selected, the value set at
F443
is used for this
parameter.
Settings:
VI/II
RR
RX
RX2 (option)
Setting
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — Setting
Changeable During Run — Yes
Regeneration Torque Limit Setting #1
Program
⇒
Torque Setting Parameters
⇒
Torque Limit Settings
⇒
Manual Settings
This parameter provides a value to be used as the Regeneration Torque Limit
#1 if Setting is selected at
F442
.
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Driving Torque Limit #2
Program
⇒
Torque Setting Parameters
⇒
Manual Torque Limit
Settings
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
F440
F444