Preset Speed Direction #12
Program
⇒
Pattern Run Control Parameters
⇒
Preset Speeds
Determines the forward/reverse setting for the #12 Preset Speed
(
F291
).
Settings:
Forward
Reverse
Direct Access Number — F392
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
Preset Speed Direction #13
Program
⇒
Pattern Run Control Parameters
⇒
Preset Speeds
Determines the forward/reverse setting for the #13 Preset Speed
(
F292
).
Settings:
Forward
Reverse
Direct Access Number — F393
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
Preset Speed Direction #14
Program
⇒
Pattern Run Control Parameters
⇒
Preset Speeds
Determines the forward/reverse setting for the #14 Preset Speed
(
F293
).
Settings:
Forward
Reverse
Direct Access Number — F394
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
Preset Speed Direction #15
Program
⇒
Pattern Run Control Parameters
⇒
Preset Speeds
Determines the forward/reverse setting for the #15 Preset Speed
(
F294
).
Settings:
Forward
Reverse
Direct Access Number — F395
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
Vector Motor Model Autotune Command
Program
⇒
Motor Parameters
⇒
Vector Motor Model
This parameter sets the Autotune command status.
Settings:
Autotune Disabled
Reset Motor Defaults
Enable Autotune on Run Command
Direct Access Number — F400
Parameter Type — Selection List
Factory Default — Autotune Disabled
Changeable During Run — No
Vector Motor Model Slip Frequency Gain
Program
⇒
Motor Parameters
⇒
Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Direct Access Number — F401
Parameter Type — Numerical
Factory Default — 0.60
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.55
F392