24
G7 ASD Operation Manual
II — The function of the II input is to receive a 4 – 20 mA input signal that controls a 0 – 80 Hz output.
This input terminal may be programmed to control the speed or torque of the motor and may not be used
when using the VI input. Also, the gain and bias of this terminal may be adjusted (see
F201
–
F204
).
VI — The function of the VI input terminal is to receive a 0 – 10 VDC input signal that controls a
0 – 80 Hz output. This input terminal may be programmed to control the speed or torque of the motor and
may not be used when using the II input. Also, the gain and bias of this terminal may be adjusted (see
F201
–
F204
).
P24 — +24 VDC @ 50 mA power supply for customer use.
PP — The function of output PP is to provide a 10 VDC output that may be divided using a potentiometer.
The tapped voltage is applied to the RR input to provide manual control of the RR programmed function.
OUT1 — The default setting for this output terminal is the Output Low Speed indicator. This output
terminal may be programmed to provide an indication that 1 of 60 possible events has taken place. This
function may be used to signal external equipment or to activate the brake (see
F130
). The OUT1 contact
is rated at 2A/250 VAC.
OUT2 — The default setting for this output terminal is the ACC/DEC Complete indicator. This output
terminal may be programmed to provide an indication that 1 of 60 possible events has taken place. This
function may be used to signal external equipment or to activate the brake (see
F131
). The OUT2 contact
is rated at 2A/250 VAC.
FP — The default function of this output terminal is to output a series of pulses at a rate that is a function
of the output frequency of the ASD. As the output frequency of the ASD goes up so does the FP output
pulse rate. This terminal may be programmed to provide output pulses at a rate that is a function of the
output frequency or the magnitude of any 1 of the 31 the functions listed in
Table 7 on pg. 61
(see
F676
).
AM — This output terminal produces an output current that is proportional to the output frequency of the
ASD or of the magnitude of the function assigned to this terminal. The available assignments for this
output terminal are listed in
Table 7 on page 61
. For further information on this terminal see
F670 on pg.
163
.
FM — This output terminal produces an output current that is proportional to the output frequency of the
ASD or of the magnitude of the function assigned to this terminal. The available assignments for this
output terminal are listed in
Table 7 on page 61
. For further information on this terminal see
F005 on pg.
60
.
FLC — FLC is the middle leg of a single-pole double-throw (relay) switch. This FLC contact of the relay
is switched between FLB and FLA. This contact may be programmed to switch between FLB and FLA as
a function of any 1 of the 60 conditions listed in
Table 9 on page 81
(see
F132
and
Figure 5 on pg. 24
).
FLB — One of two contacts that, under user-defined conditions, connect to FLC (see
Figure 5 on pg. 24
).
FLA — One of two contacts that, under user-defined conditions, connect to FLC (see
Figure 5 on pg. 24
).
Note:
The FLA and FLC contacts are rated at 2A/250 VAC. The FLB contact is rated at 1A/
250 VAC.
CC — Control common (Do Not connect to Earth Gnd).
Figure 5. FLA, FLB, and FLC switching contacts shown in the de-energized state.
Note:
The relay is shown in the Faulted or
de-energized condition. During
normal system operation the relay
connection is FLC-to-FLA.