5.5.5 JOG Operation
JOG operation is a mode that operates the inverter while JOG command is inputted, and has the following
features.
(1) Forward output by forward JOG command (F), reverse output by reverse JOG command (R).
(2) The 1st speed, 2nd speed and 3rd speed are provided for each forward JOG command and reverse JOG
command. Use 2nd speed command (2S) to select 2nd speed and 3rd speed command (3S) to select 3rd
speed.
(3) Each F, R, 2S and 3S command is inputted via sequence input or PI/O input.
Also, the function has the following restrictions.
(4) Startup command (EXT) is given priority over JOG command.
In addition, JOG command is detected at the rise of the signal, so JOG operation is not performed even
when startup command is turned off after start command cancels JOG operation.
(5) The command which is previously inputted among F and R, 2S and 3S is given priority.
Setting parameters shown in Table 5.5.2 are speed reference of JOG operation. JOG operation command
and an operation pattern is shown in Fig. 5.5.5.
Table 5.5.2 JOG Operation Command and Speed Reference Settings
Type
Forward JOG
command F
Reverse JOG
command R
2nd speed
command 2S
3rd speed
command 3S
Speed reference
setting
Forward JOG
1st speed
1 0 0 0
$CR_JOG_FJ1S
Forward JOG
2nd speed
1 0 1 0
$CR_JOG_FJ2S
Forward JOG
3rd speed
1 0 0 1
$CR_JOG_FJ3S
Reverse JOG
1st speed
0 1 0 0
$CR_JOG_RJ1S
Reverse JOG
2nd speed
0 1 1 0
$CR_JOG_RJ2S
Reverse JOG
3rd speed
0 1 0 1
$CR_JOG_RJ3S
Forward JOG
command F
Speed reference
Reverse JOG
command R
3rd speed
command 3S
2nd speed
command 2S
Startup command
EXT
0
$CR_JOG_FJ3S
$CR_JOG_FJ2S
$CR_JOG_FJ1S
$CR_JOG_RJ1S
$CR_JOG_RJ2S
$CR_JOG_RJ3S
0
0
0
0
0
Fig. 5.5.5 JOG Operation Command and Operation Pattern