— 69 —
6F3A4768
3.4.5 PROFIBUS Transmission Specifications
PROFIBUS hardware specifications are shown in below.
Table 3.4.12 PROFIBUS Hardware Specifications
Item
PROFIBUS transmission board type
ARND-8130A
Connector type
9 pin D-Sub connector
Shielded twisted pair copper wire cable type A
Cable
specification
Resistance
Capacitor
Loop resistance
Diameter
Cross-section
135 ~ 165
Ω
30 pf/m
110
Ω
/km
0.64 mm
> 0.34 mm
2
Transmission
distance
Depending on transmission speed
Transmission speed [kbps]
Maximum length per segment [m]
9.6, 19.2, 45.45, 93.75
1200 m
187.5
1000
m
500
400
m
1500
200
m
3000, 6000, 12000
100 m
3.4.5.1 PROFIBUS Connection
Example of connection is shown in Fig. 3.4.13.
Drive
equipment
ARND-8130A
T3H
T3H-PROFIBUS master
T-PDS tool
AB-DT-PDP
(HMS)
Drive
equipment
ARND-8130A
AB-DT-PDP
(HMS)
PROFIBUS Cable
Fig. 3.4.13 Examples of PROFIBUS Connection