— 38 —
6F3A4768
Table 2.3.15 Main Protective Functions of TMdrive-P30
Detection *1
Linked operations *2
Major fault
Medium
fault
Minor
fault
Item Abbreviation
Hardware Software Current
input
breaker trip
Gate block
stop
Stop
request
Alarm
Related setting
AC overcurrent
OCA
Yes
Yes
Yes
$CP_OCA
DC overvoltage
OVP, OVN
Yes
Yes
$CP_OV
DC overcurrent
OCD
Yes
Yes
Yes
CPU failure
CPU_A,CPU_M
Yes
Yes
Yes
Gate power supply failure GDM_F
Yes
Yes
External safety switch
UVS
Yes
Yes
Panel safety switch
P_SW
Yes
Yes
Phase fuse blown
F_U,V,W
Yes
Yes
Yes
Capacitor fuse blown
F_C
Yes
Yes
Yes
Main power supply failure MPSF
Yes
Yes
Yes
$CP_VREC_MPSF
Power supply
synchronization PLL error
PLL
Yes
Yes
Yes
Equipment overheat timer OH_T
Yes
Yes
Yes
$TIME_OH
External interlock
IL
Yes
Yes
Transmission error
TL_F1~4
Yes
Yes
External equipment
electrical ready condition
UVA_EXT
Yes
Yes
Equipment ventilation fan
stop timer
C_FN_T
Yes
Yes
$TIME_CFAN
Control power source
failure
CPSF
Yes
Yes
$CP_PSF
Current limit timer
CL_T
Yes
Yes
$TIME_CL
DC voltage drop (P,N)
UVP, VVN
Yes
Yes
Overload (5 min)
OL5
Yes
Yes
$CP_RMS_5,
$CP_RMS_A
Overload (20 min)
OL20
Yes
Yes
$CP_RMS_20,
$CP_RMS_A20
AC input breaker open
timer
ACSW_T
Yes
Yes
Grounding detection timer GR_T
Yes
Yes
$CP_GDI
Equipment overheat
OH
Yes
Yes
Equipment ventilation fan
stop
C_FN
Yes
Yes
(Yes)
Initial charge failure
PRE_F
Yes
Yes
(Yes)
Current limit alarm
CL_TA
Yes
Yes
(Yes)
Overload alarm
OL_A
Yes
Yes
Grounding detection
alarm
GR_A
Yes
Yes
(Yes)
StockCheck.com