— 143 —
6F3A4768
The setup of shared motion may not be completed normally at the beginning of adjustment at field. In this case,
setting parameter change cannot be performed using 2S signal. Therefore, the method that save parameters to
A bank and B bank EEPROM from a setting parameter file at the beginning of adjustment at field is shown in Fig.
5.5.8.
Turn on the operation panel
INTERLOCK switch
Download setting parameters from
"usual use machine" (parameter used when
2S signal is 0) parameter file with the tool
Check the below settings with the tool
$FLG_CHGSYS :
12345(In the case of 2S input by DI)
6789(In the case of 2S input by LAN)
$ASPR_G_SEL
≠
3
2S setting of $MSK_DI1
(In the case of LAN use,
2S setting of $MSK_SERSEQ1)
Input CHGSYS=AAAA(h) with the
tool (Select A bank)
Execute saving from SRAM to
EEPROM with parameter
management of the tool
Input CHGSYS=BBBB(h) with the
tool (Select B bank)
Download setting parameters from "change
use machine" (parameter used when 2S
signal is 1) parameter file with the tool
Execute saving from SRAM to
EEPROM with parameter
management of the tool
Check the below settings with the tool
$FLG_CHGSYS :
12345(In the case of 2S input by DI)
6789(In the case of 2S input by LAN)
$ASPR_G_SEL
≠
3
2S setting of $MSK_DI1
(In the case of LAN use,
2S setting of $MSK_SERSEQ1)
Turn off the operation panel
INTERLOCK switch
Fig. 5.5.8 The Setting Parameter Save Method to Each Bank of EEPROM
Bit signal B_CPUA_CHG_SET (bit 13 of CPUA_STS1) indicates which bank the inverter is actually selecting.
When B_CPUA_CHG_SET is 0, bank A is selected. When B_CPUA_CHG_SET is 1, bank B is selected.