![THK TJU Instruction Manual Download Page 126](http://html1.mh-extra.com/html/thk/tju/tju_instruction-manual_1107536126.webp)
10. Technical
Materials
4.
Sample program
10-7
TNU
4-2
CC-Link sample program
This section describes the sample program to operate the driver controller connected to the
TNU from the upper-level PLC.
4-2-1
Procedures to driver controller operations
Configuration
Type
Manufacturer
Remark
PLC
Q02HCPU
Mitsubishi Electric
Corporation
-
CC-Link master
QJ61BT11N
Mitsubishi Electric
Corporation
-
Network unit (remote device)
TNU-CC
THK
Station number 1
I/O unit (remote IO)
AJ65SBTB32-BDT2 Mitsubishi Electric
Corporation
Station number 5
Branch unit
TJU
THK
-
Driver controller
TSC
THK
ID=0
CC-Link device allocation information
Remote input (RX)
X1000
Remote output (RY)
Y1000
Remote register (RWr)
W0
Remote register (RWw)
W100
SET W100.F
W0.E
W0.F
W0.D
END
EMGS (E), ALM (F) ON
↓
Turn SVON (F) and
PAUSE (E) ON
Rising of SVRDY (D)
↓
Turn HOME (C) ON
SET W100.D
SET W100.C
Servo on
Zero return command
W0.A
Rising of HEND (A)
↓
Turn HOME (C) OFF
RST W100.C
Zero return command is released