ULTRAFLOW 150 GAS FLOW AND TEMPERATURE MONITOR
7.2 SITE SELECTION
Without question, the single most important factor affecting overall
performance of any continuous monitoring device is that of site selection.
If this decision is not made prudently, then monitor accuracy and
reliability will suffer.
7.2.1 Representative Sampling Location
Since the Ultraflow 150 uses an "across stack", non-contacting sampling
technique, it measures the average flow velocity along a path from one
transducer to another, which passes through the center of the stack or duct.
Although this technique is inherently more representative than point
sampling schemes, complex flow patterns in the vicinity of bends or
obstructions may potentially cause the monitor's sample path to be
unrepresentative of the total flow velocity and volume. Teledyne Monitor
Labs Installation Drawing ULTRAFLOW 150 FLANGE
INSTALLATION contains minimum recommended location distances
from upstream and downstream bends, which should allow for proper
sampling. However, due to the complexity of the fluid dynamics of these
types of gas streams and their dependence on individual site geometry, the
burden of responsibility for testing to determine the flow characteristics at
the site location is solely that of the user. Please consult the Teledyne
Monitor Labs factory for details.
7.2.2 Access to Sampling Location
Ease of access to the stack mounted equipment is a factor that is nearly
always underrated when deciding on an installation site. If the monitor
location is only accessible via vertical ladders with extensive climbing
involved or in exposed outside areas where maintenance personnel are
subject to extremes of wind, precipitation, or temperature, then monitor
maintenance will suffer adversely in the long term. Without proper
maintenance, reliability decreases and the access problems extend monitor
outage during repair.
7.2.3 Environmental Conditions at the Sampling Location
The other important factor involved in site selection is to consider the
potential conditions of the area where the Transducer Interface Enclosure
and Purge System will be located. Ambient conditions at this location
must not exceed the temperature range specified in the Teledyne Monitor
Labs specifications. This will void the Teledyne Monitor Labs warranty.
The presence of potentially corrosive or toxic gases in the ambient air in
the vicinity of the Transducer Interface Enclosure and Purge Air System
may deteriorate the condition of electrical connections such as IC sockets,
connectors, etc., in the electronic assembly. This may also greatly reduce
7-2
Summary of Contents for ULTRAFLOW 150
Page 2: ...DOCUMENT NO 1900 0100 01 REV E ...
Page 24: ...ULTRAFLOW 150 GAS FLOW AND TEMPERATURE MONITOR This page intentionally left blank 4 6 ...
Page 75: ...SECTION 7 0 INSTALLATION This page intentionally left blank 7 7 ...
Page 76: ......
Page 85: ...SECTION 8 0 SYSTEM CALIBRATION AND ADJUSTMENT This page intentionally left blank 8 9 ...
Page 86: ......
Page 89: ...APPENDIX A SITE SPECIFICATION DATA SHEETS ...
Page 90: ...ULTRAFLOW 150 GAS FLOW AND TEMPERATURE MONITOR This page intentionally left blank ...
Page 95: ...APPENDIX B MAINTENANCE CHECK SHEETS ...
Page 96: ... This page intentionally left blank ...
Page 101: ...APPENDIX C SPARE PARTS ...
Page 102: ... This page intentionally left blank ...
Page 105: ......
Page 106: ...APPENDIX D DRAWINGS ...
Page 107: ... This page intentionally left blank ...
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ...APPENDIX E ENHANCED SERIAL PORT COMMUNICATION PROTOCOL ...