
ULTRAFLOW 150 GAS FLOW AND TEMPERATURE MONITOR
3.
WITH CAL = EXP:
Calibration data will be sent to that output
when a calibration request is processed. Scaling for the
SPANHIGH and SPANLOW calibration data will be the same as
the Normal mode scaling entered under VALUE AT ZERO
SCALE and VALUE AT FULL SCALE. However, scaling for
ZERO calibration data will be ±10% of the VALUE AT FULL
SCALE.
6.5.2 DIGITAL INPUTS
The Multi I/O can issue mode change commands to the Transducer
Interface Enclosure (TIE) based on the status of digital inputs one through
six. These are known as the CAL REQUEST inputs. They can initiate the
various calibration modes for each TIE. (
Both paths within a TIE follow
the same mode change request.
) By controlling which input is activated,
the operator can construct an “on-demand” calibration cycle to meet the
systems needs. There are also inputs that will initiate the automatically
timed internal CAL cycle for each TIE. See Table 6-7, Digital Inputs for
Calibration Request.
The Multi I/O analog outputs can be forced to diagnostic status (TEST
FULL SCALE, TEST ZERO SCALE, etc.) from two sources: digital
inputs seven and eight, and the Enhanced Remote Display keypad. The
operation of the digital inputs is described in Table 6-8, Digital Inputs for
Analog Output Control. The keypad display commands are described in
the section on menu structure. If the Multi I/O receives conflicting or
overlapping requests for the analog outputs, its priority handler will assign
requests from the digital inputs top priority and the keypad requests from
the Enhanced Remote Display second priority.
6.5.3 DIGITAL OUTPUTS
The Multi I/O Board’s eight digital outputs (relays) can be configured to
activate on any one of over eighty parameters. These are listed in Table 6-
9, Parameters for Relay Assignment. They fall into three categories:
Alarm indicators
Fault indicators
Output mode indicators
Standard practice is to assign a relay to each of the four CAL modes.
These signals will then indicate when and what data is present on the
analog outputs for data logging purposes. For more information on
software function see the Operational Modes of the Transducer Interface
Enclosure section (Section 4.0).
6-26
Summary of Contents for ULTRAFLOW 150
Page 2: ...DOCUMENT NO 1900 0100 01 REV E ...
Page 24: ...ULTRAFLOW 150 GAS FLOW AND TEMPERATURE MONITOR This page intentionally left blank 4 6 ...
Page 75: ...SECTION 7 0 INSTALLATION This page intentionally left blank 7 7 ...
Page 76: ......
Page 85: ...SECTION 8 0 SYSTEM CALIBRATION AND ADJUSTMENT This page intentionally left blank 8 9 ...
Page 86: ......
Page 89: ...APPENDIX A SITE SPECIFICATION DATA SHEETS ...
Page 90: ...ULTRAFLOW 150 GAS FLOW AND TEMPERATURE MONITOR This page intentionally left blank ...
Page 95: ...APPENDIX B MAINTENANCE CHECK SHEETS ...
Page 96: ... This page intentionally left blank ...
Page 101: ...APPENDIX C SPARE PARTS ...
Page 102: ... This page intentionally left blank ...
Page 105: ......
Page 106: ...APPENDIX D DRAWINGS ...
Page 107: ... This page intentionally left blank ...
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ...APPENDIX E ENHANCED SERIAL PORT COMMUNICATION PROTOCOL ...