5-15
764333-675
5.3 OTHER FAULTS
5.3.1
Ground Fault Interrupt (GFI) Trip
Description
– A GFI measures the difference in
current flow between the hot and neutral lines of a
circuit. Normally both are identical; however, if there
is current leakage to ground from the hot line, the GFI
senses the imbalance and
trips
.
The typical trip point of a GFI is 4 to 6 mA, and since
this is a very small level of imbalance, it will require
component isolation to locate the cause.
Establish if the GFI trips as soon as the unit turns on,
or if it occurs in cycle. If trip occurs when turned on, it
may be necessary to isolate components one at a time.
When doing so, turn the unit ON to see if the GFI trips.
If trip occurs in cycle, the trip may be occurring when
a specific component is energized; if so, use the service
mode/hand terminal to manually activate individual
components until the source of trip is located.
Action:
1. Verify proper operation of GFI using ground fault
tester – if OK, continue with component isolation,
otherwise, replace GFI.
2. If trip occurs in cycle – use service mode/hand
terminal to operate components individually until
trip source is located.
3. If trip occurs when powered up – isolate individual
components manually until fault is located.
5.3.2
Water Spills from SYSTEM 1E Processor
Action:
Check the following items.
1. Drip pan full of water?
2. Is chamber filling?
a.
Faulty LS3 – repair.
b.
SOL5 or SOL7 leaking – repair.
c.
Are instruments loaded incorrectly – reload.
d.
Is water pressure >60 psi – reduce.
e.
Back pressure in the drain – repair.
f.
Faulty CK2, CK3 – repair.
g.
Header block – replace lid.
Summary of Contents for SYSTEM 1E
Page 1: ...MAINTENANCE MANUAL SYSTEM 1E Liquid Chemical Sterilant Processing System 12 09 10 P764333 674 ...
Page 3: ......
Page 71: ...5 19 764333 675 Figure 5 2 Analog Cable Assembly Pin Out Locations ...
Page 74: ...5 22 764333 675 Figure 5 7 DC Power Supply Harness Pin Out Locations PS P1 ...
Page 96: ...7 19 764333 675 Figure 7 17 Aquafine STERIUV5 Control Panel The Control Panel A B 3 2 1 ...
Page 108: ......
Page 110: ...ii 764333 676 Example 1 How To Use IPB Page Typical ...
Page 119: ...10 764333 676 Figure 1 SYSTEM 1E Piping Schematic ...
Page 121: ...12 764333 676 Figure 2 SYSTEM 1E Complete 4 3 2 ...
Page 128: ...19 764333 676 Figure 5 Fluid and Air Components 2 of 2 51 53 48 47 50 49 52 ...
Page 133: ...24 764333 676 Figure 7 Float Block Switch Assembly 1 5 8 7 5 4 10 4 2 6 9 9 3 CK2 CK3 LS3 CK1 ...
Page 137: ...28 764333 676 Figure 9 Drain Block Assembly 3 4 5 6 7 3 1 2 8 CK8 TC3 ...
Page 143: ...34 764333 676 Figure 12 Bulkhead Connector Assembly 1 2 2 2 3 1 1 3 5 4 4 6 ...
Page 155: ...46 764333 676 Figure 18 Harness Cable Assemblies 1 of 2 1 2 3 4 5 6 P10 PT1 P5B P11 P2 P5A ...
Page 166: ......
Page 167: ......
Page 168: ......
Page 169: ......
Page 170: ......