18
Parameter – time of Smoke alarm
Time in which the gate remains in alarm „Smoke“ i.e. in
position partly opened before closing again:
•
5–999 seconds
•
„-„ = time unlimited
Default = 10
Parameter – length of opening time in case of Smoke alarm
activation
•
0–100% gate width
•
„-„ = according to the setting of middle position
Note: When we have end switches NES it is possible to set only „-“
and position follows the setting of middle position.
Default = 50 %
Parameter – do not monitor OSE / Ledge 8K2
The width from which the safety edge of OSE
is not monitored to prevent the unwanted opening before the contact with stop profile.
Range of values: 1–100 % from 10 promiles of gate width
Default = 30 %
Parameter – correction of the end position “opened”
Range of values: -99 – +99 % from 1 % gate height
Default = 0
Parameter – correction of the end position “closed”
Range of values: -99 – +99 % from 1 % gate height
Default = 0
Parameter – selects type of motor for correct setting of
frequency inverter
We select the type of motor and the control box enters,
into the frequency inverter, the appropriate parameters
of the particular motor for its proper and smooth operation.
Note: Control boxes FSTronic IRC-FI are supplied in two sizes of frequency inverter see
the table, point 2.
Value „r“
Motor type
Type od sensor
Power of
inverter
1
EPO 120W
IRC
2 A
2
EPO 180W
IRC
2 A
3
EPO 250W
IRC
4 A
Summary of Contents for FSTronic IRC-FI
Page 36: ...www somati system cz 36 12 2 FSTronic IRC FI CONTROL BOARD DPS ...
Page 38: ...www somati system cz 38 12 4 FSTronic IRC FI CONNECTION OF FIRE DETECTORS ...
Page 39: ...www somati system cz 39 12 5 FSTronic IRC FI Connection aof additional battery module ...
Page 42: ...www somati system cz 42 GridScan PRO SY 2000 FSS GridScan PRO SY 2000 LO ...
Page 43: ...www somati system cz 43 GridScan MINI FSS GridScan MINI PNP NPN ...