20
Parameter – field of deceleration closed possition
Range of values: 1–10 %
Value of the length distance before reaching bottom end possition.
Value is shown in percent of traveling distance.
Note: In case of roller gate influenced by non linearity of roll up diameter.
Default = 3 %
Parameter – cross optocell
Possible to set functionality of safety sensor (input X2:+,X2:2) for cross connection.
Opportunity to use two optocells with cross safety beams under door leave. During closing
gate will be functionality of safety sensor deactivated when reached position set by LS1
so moving door leaf will not activate the sensor. Necessary to set right possition LS1.
When this parameter set on value 1 then safety sensor between LS1 and bottom
possition is not active. (Typical application for conveyors – vertically moving door)
Range of values:
•
0 = normal
•
1 = cross optocell
Default = 0
Parameter – speed in alarm mode
Range of values: 20–150 %
Value showes how many percents from maximum frequency 50 Hz
(primary set on frequency inverter) will be the speed in case of alarm
(100 % = 50 Hz).
By reducing of this speed possible to reach longer operation from battery backup.
Default = 40 %
Parameter - service period (cycles)
service period 1 - 50 cycles, steps in 1000 cycles
Note: 0 = 10 cycles
Default = 3 (3000 cycles)
Parameter - conveyor confirmation
type of reaction when activated input “SMOKE” (X2:43 and X2:44)
0 = standard function “SMOKE”
1 = conveyor confirmation - in case of alarm and running time delay can be gate closed
immediately when activated this input. When conveyor is clear gate can close quicker.
Default = 0
Parameter - initial alarm braking time
Allows you to select the length of the stop time in case of the FIRST
activation of the safety device during closing in alarm.
Range of values: 1–999
second/s Default = 10
Summary of Contents for FSTronic IRC-FI
Page 36: ...www somati system cz 36 12 2 FSTronic IRC FI CONTROL BOARD DPS ...
Page 38: ...www somati system cz 38 12 4 FSTronic IRC FI CONNECTION OF FIRE DETECTORS ...
Page 39: ...www somati system cz 39 12 5 FSTronic IRC FI Connection aof additional battery module ...
Page 42: ...www somati system cz 42 GridScan PRO SY 2000 FSS GridScan PRO SY 2000 LO ...
Page 43: ...www somati system cz 43 GridScan MINI FSS GridScan MINI PNP NPN ...