5
2.
Po
wer cable – terminal block X4 terminals L,N,PE
Necessary to connect all wires including
grounding. Without grounding (PE) can be unit
damaged.
After connecting the switchboard to the mains,
the batteries can be connected by inserting a
fuse into the disconnector, see point 3.7
3.
Connect terminals EPS - fire contact
(X2:+ and X:10) by default set as input NC contact - can be
changed by parameter (default setting when the door is
open, the door is still in alarm). Originally supplied with the
wire jumper marked “fire contact”.
4.
Terminals of safety brake - (X1:13 and X1:14)
or the IRC_FI version, this input is used to block the motor in
the closed position. The input is NO, if it closes in the closed
position then the motor is blocked - it is used for input of the
inductive sensor of the door hook lock. Do not connect the
terminals
5.
Install key switch - due to transport is delivered disassembled
Note:
For version compact key switch is not part of standard
delivery. Can be additionally added.
2.
!
4.
5.
5.