2
1.
Basic data and power supply
Casing size:
400 x 400 x 210 mm (W x H x D)
Weight:
23 kg (without batteries 18kg)
Installation:
vertically on the wall
Connection:
the inlets and outlets of the power and control
circuits are via PG bushings on the underside of the
switchboard
Voltage system:
1-N-PE, 50 Hz, 1 x 230 V, TN-S
Input fusing:
see table with versions and sizes according to
frequency invertor
! if RDC (Residual current device) is udes
sensitivity not lees than 100mA !!
Unit supply current:
0,3A without external devices and accumulators
0,6A without external devices and with charging
Of accumulators. Current under load acc. to size
Operating voltage:
24 VDC
Output voltage for ext. devices:
max.24 VDC/1,2A – max for each output see details
of outputs – sum cannot exceed max. 1,2A
Output voltage for motor brake:
103 VDC/0,3A
Output voltage for motor:
0÷125 Hz, 3 x 0÷230 VAC
Control inputs:
24V/10mA pro bezpotenciální kontakty
Accumulators:
part of control unit – 2pcs 12V/7-10Ah
additionals – up to 3 sets of 2pcs 12V/7-10Ah
Fusing of accumulators:
ceramic fuse 10x38 gG in disconnector
tube fuse F6,3A in transformator SCP-35-24
Operating temperature:
+10°C up to +35°C, at temperatures above + 25 ° C
and below + 15 ° C the battery life decreases.
Exceptionally, it can be operated at lower
temperatures up to -5 ° C, provided that it is
permanently connected to a power supply that
provides heating of the circuits.
Air humidity:
max 93% without condensation
Degree of protection:
IP 54
Protection against electric shock is made according to ČSN 33 2000-4-41 by automatic
disconnection of defective part from power supply and supplementary connection of safety
circuits.
2.
Configuration
FSTronic IRC-FI is designed to control drive of sliding (or vertically moving with counter weight)
fire gates - using asynchronous motors (eg. EPO) with system of battery back up.
Power supply of control box is backed up by batteries to close gate (or to open gate)
in case of power failure, using special battery backup system and frequency inverter. In case
of power failure gate stays in position, in which the power failure occurred, for the set time
Summary of Contents for FSTronic IRC-FI
Page 36: ...www somati system cz 36 12 2 FSTronic IRC FI CONTROL BOARD DPS ...
Page 38: ...www somati system cz 38 12 4 FSTronic IRC FI CONNECTION OF FIRE DETECTORS ...
Page 39: ...www somati system cz 39 12 5 FSTronic IRC FI Connection aof additional battery module ...
Page 42: ...www somati system cz 42 GridScan PRO SY 2000 FSS GridScan PRO SY 2000 LO ...
Page 43: ...www somati system cz 43 GridScan MINI FSS GridScan MINI PNP NPN ...