11
It is possible to terminate the calibration by pressing knob button – however, the calibration
of time is not set and the unit cannot work automatically.
3.2.
Complete reset of unit
If necessary it is possible to make complete reset (e.g. in case of using on other motor).
Deletes end positions calibration of the time all parameters will be set to default and
parametr “r” will be set for weakest motor r=1.
Deleting is possible only from STOP state, on display must be shown
Press and hold knob button – after approx. 20s the delete operation
starts, on display is shown “ErSt”. Reset must be confirmed.
a)
If we press knob button – we return to STOP state without deleting)
b)
If we turn the knob, select “YES” and press knob button – the deletion is accomplished
and we return to “STOP”.
c)
If we turn the knob, select ESC and press knob button – we return to STOP
without deletion.
4.
Connection of other external devices
After testing the setting of end positions (IRC) it is possible to continue with connection of
other external devices.
Control box FSTronic DES-FI is standardly equipped with keyboard buttons „Open“ and
„Close“, which can be used to open the gate in “Dead man” mode. For automatic operation
(one- press start) upwards, it is necessary to connect terminals X2:+ and X2:3 by connection
or safety device. If it is possible to hang on the surface of gate leaf or to pass an object
through the gate, it is necessary to add a safety device “upper safety sensor” to maintain
automatic operation
Automatic operation close is activated by connecting safety sensor „lower safety sensor“
with terminals X2:+ and X2:2 („lower safety sensor“) or by connecting optical safety edge
OSE with terminals X2:G and X2:W and X2:B (ATTENTION - OSE safety bar must be
activated, see 5.2.1 - DIP8. If the safety sensor is disconnected (or
OSE or contact strip is
activated) during closing, gate moves back and stops (see setting of DIP6 and selection of
parameter „4“).
In case the „lower safety sensor“ is disconnected (or OSE or contact strip is activated)
permanently, it is possible to close the gate in “Dead man” mode. “Lower safety sensor” has no
influence on opening of gate.
It is also possible to connect safety contact strip of the system with closed loop by resistance
(8,2kΩ) – this function is identical with the function of OSE or “lower safety sensor”. If the contact
strip is not connected, terminals X2:39 and X2:40 has to be connected to resistance 8,2kΩ -
without the resistance the automatic operation does not work.
When pull switch (X2:8) is activated, gate opens into the open end position and remains
in this position for a time set in parameter „6“, then the gate automatically closes.
Control Step-by-step (X2:7) enables to open and close gate with a single button. When we press
Summary of Contents for FSTronic IRC-FI
Page 36: ...www somati system cz 36 12 2 FSTronic IRC FI CONTROL BOARD DPS ...
Page 38: ...www somati system cz 38 12 4 FSTronic IRC FI CONNECTION OF FIRE DETECTORS ...
Page 39: ...www somati system cz 39 12 5 FSTronic IRC FI Connection aof additional battery module ...
Page 42: ...www somati system cz 42 GridScan PRO SY 2000 FSS GridScan PRO SY 2000 LO ...
Page 43: ...www somati system cz 43 GridScan MINI FSS GridScan MINI PNP NPN ...